Module 4 kênh đầu vào nhiệt độ RTD (PT100, JPT100) Cimon CM1-RD04A
Module 4 kênh đầu vào nhiệt độ RTD (PT100, JPT100) Cimon CM1-RD04A
Temperature
Using CANbus, exchanges data real-time.
The temperature converted by a platinum resistance temperature detector of Pt100 of Jpt100 or Pt1000 or Ni1000 can be displayed in ℃ or ℉, and the temperature values can be processed as digital values up to the first decimal place.
The converted temperature data are converted to 16bit binary data, which can be processed as digital values. The temperature in the range from -200℃ to 600℃ are converted to the values from 0 to 16000(-8000~8000).
The range of temperature is from -250℃ to 650℃, and the range of digital value is from -192 to 16191.
If Min and Max. temperature values are set up, the min. value will be converted to 0 (-8000) and the max. value is 16000(8000).
Each channel can detect the breaking of resistance temperature, cables, and the excess of measuring range.
There are 4 channels to connect PT100, JPT100, PT1000 or Ni1000.
The number of modules used on one base is not limited.
LED is lighted in normal status, and blinks at the intervals of 0.2 second in error status.
RTD
|
|
||
---|---|---|---|
Available RTD |
CM1-RD04A Pt100 |
CM1-RD04B Pt1000 (DIN EN 60751) |
|
Range of Temperature Input |
Pt100:-200.0°C to 600°C |
Pt1000:-200.0°C to 600°C |
|
Digital Output |
Digital converted value : 0~16,000 (-8000~8000) |
||
Detecting the breaking of wires |
3 wires per channel |
||
Accuracy |
±0.1%[Full Scale] |
||
Max.Conversion Rate |
50ms / 1ch. |
||
Number of Temperature Inputs |
4 Ch. / 1 module |
||
Insulation |
Between input terminal and PLC Power : Photo-Coupler |
||
Contact terminal |
18-points Terminal Block |
||
No. of Occupied Points |
16 Points |
||
Internal |
+5V |
50 |
|
+15V |
30 |
||
-15V |
10 |