Module RS-485 DCON 1 kênh đầu vào RTD ICP DAS I-7013 CR

Thương hiệu: ICP DAS | Tình trạng: Còn hàng
Liên hệ

1-ch RTD Input Module

Gọi +84 904251826 để được trợ giúp

Module RS-485 DCON 1 kênh đầu vào RTD ICP DAS I-7013 CR

Features

• 1-channel RTD Input
• Lead Resistance Elimination for 3/4-wire Connection
• Open Wire Detection
• 3000 VDC Intra-module Isolation
• Dual Watchdog
• Wide Operating Temperature Range: -25 to +75°C

Introduction

The I-7013(D) and M-7013P(D) is a 1-channel RTD Input module that is used for measuring temperatures via an RTD sensor and supports Pt100, Ni120, and Pt1000 type sensors. The module allows 2/3/4-wire RTD connections and features open wire detection. In addition, the I-7013(D) and M-7013P(D) also includes 3000 VDC intra-module isolation and supports lead resistance elimination for 3/4-wire connections. The M-7013P and M-7013PD added support for 1-channel digital input as 50 Hz event counter and 2-channel digital output as high/low alarm. The M-7013P and M-7013PD support both the Modbus RTU and DCON protocols, which can be configured via software.

Specification

CPU Module
Watchdog Timer Yes, Module (1.6 Seconds), Communication (Programmable)

 

Isolation
Intra-module Isolation 3000 VDC

 

EMS Protection
EFT (IEC 61000-4-4) ±4 kV to Power Line
ESD (IEC 61000-4-2) ±2 kV Contact for each Terminal
Surge (IEC 61000-4-5) ±0.5 kV for Power Line

 

LED Indicators
Status 1 x Power and Communication

 

Analog Input
Channels 1
Type RTD
Sensor Type Pt100, Pt1000, Ni120
Resistance Measurement 3.2 kΩ Max.
Resolution 16-bit
Accuracy ±0.05%
Sampling Rate 10 Hz
Overvoltage Protection ±5 VDC
Individual Channel Configuration No
Open Wire Detection Yes
3-wire RTD Lead Resistance Elimination Yes

 

COM Ports
Ports 1 x RS-485
Baud Rate 1200 to 115200 bps
Data Format (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1)
Protocol DCON

 

Power
Reverse Polarity Protection Yes
Input Range +10 ~ +30 VDC
Consumption 0.7 W

 

Mechanical
Dimensions (mm) 123 x 72 x 35 (W x L x H)
Installation DIN-Rail

 

Environmental
Operating Temperature -25 ~ +75 °C
Storage Temperature -40 ~ +85 °C
Humidity 10 ~ 95% RH, Non-condensing

Download

Data sheet

Documents

Odering information

I-7013     CR  1-ch RTD Input Module using DCON Protocol (Blue Cover) (RoHS)